Question of pid-contorl on stepwise configuration
Hi team:
I have a question regarding stepwise configuration on pid-control.
I have mine setup like below.
{
"name": "Ambient_Temp",
"type": "stepwise",
"setpoint": 0.0,
"inputs": ["Ambient_Temp"],
"pid": {
"samplePeriod": 1.0,
"positiveHysteresis": 0.0,
"negativeHysteresis": 0.0,
"isCeiling": false,
"reading": {
"0": 25,
"1": 30,
"2": 35
},
"output": {
"0": 15,
"1": 15,
"2": 15
}
}
}
And, I would like to know the meaning of each field, as far as I understand from phosphor-pid-control, "setpoint" seems not used if PID type is stepwise. Is that true? The "reading" field indicates the temperature reading from the sensor "Ambient". The "output" field should indicate the duty % corresponding to the fans, or should output be RPMs? That gives me when a reading of 25 degree(whatever the unit is), the output duty of fans should set to 15%, or set to corresponding RPMs.Do I understand the fields correctly?
Thank you,
________________________________
Derek Lin
Sr. BMC Engineer
8F,66, San Chong Rd., Nankang Software Park, Taipei. Lenovo Taiwan
[Phone]+886281707411 [Email][email protected]<mailto:[email protected]>
Lenovo.com<http://www.lenovo.com/>
Twitter<http://twitter.com/lenovo> | Instagram<https://instagram.com/lenovo> | Facebook<http://www.facebook.com/lenovo> | Linkedin<http://www.linkedin.com/company/lenovo> | YouTube<http://www.youtube.com/lenovovision> | Privacy<https://www.lenovo.com/gb/en/privacy-selector/>
[ImageLogo-DCG-Honeycomb]
Quoted 43 lines · On 8/21/2019 4:36 AM, Derek Lin23 wrote:
Hi team:
I have a question regarding stepwise configuration on
pid-control.I have mine setup like below.
{
"name": "
Ambient_Temp","type": "stepwise",
"setpoint": 0.0,
"inputs": ["
Ambient_Temp"],"pid": {
"samplePeriod": 1.0,
"positiveHysteresis": 0.0,
"negativeHysteresis": 0.0,
"isCeiling": false,
"reading": {
"0": 25,
"1": 30,
"2": 35
},
"output": {
"0": 15,
"1": 15,
Quoted 8 lines
"2": 15
}
}
}
I don't use the json configuration, so you'll have to do a bit of a comparison of apples and oranges, but here is an example of a stepwise configuration: https://github.com/openbmc/entity-manager/blob/08a5b175eec81c53506709fda8a7c168748cc22d/configurations/R1000%20Chassis.json#L577
Reading is the reading of the sensor, and output is the setpoint given to the fan pid. Depending on how you configure your system this can either be a percent, or it can be a tach reading. When a sensor reaches a reading, the corresponding output is given to the fan controller as a setpoint. So it my example, when we reach a temp of 30 degrees, the setpoint of 60 is given to the fancontroller. This 60 is unitless and depends on how the fan controller configuration is implemented how it affects the fans.
-James
Quoted 30 lines
And, I would like to know the meaning of each field, as far
as I understand from phosphor-pid-control, “setpoint” seems not used if PID type is stepwise. Is that true? The “reading” field indicates the temperature reading from the sensor “Ambient”. The “output” field should indicate the duty % corresponding to the fans, or should output be RPMs? That gives me when a reading of 25 degree(whatever the unit is), the output duty of fans should set to 15%, or set to corresponding RPMs.Do I understand the fields correctly?
Thank you,
------------------------------------------------------------------------
*Derek Lin*
Sr. BMC Engineer
8F,66, San Chong Rd., Nankang Software Park, Taipei. Lenovo TaiwanPhone+886281707411
[email protected] <mailto:[email protected]>Lenovo.com <http://www.lenovo.com/>
Twitter <http://twitter.com/lenovo> | Instagram <https://instagram.com/lenovo> | Facebook <http://www.facebook.com/lenovo> | Linkedin <http://www.linkedin.com/company/lenovo> | YouTube <http://www.youtube.com/lenovovision> | Privacy <https://www.lenovo.com/gb/en/privacy-selector/>ImageLogo-DCG-Honeycomb